Condenser disconnect, cover open
What's wrong here?
- Nothing. This installation is compliant
- 12 AWG copper conductors may not be protected by 30 A fuses
- The fuses must not exceed the 17.6 A minimum circuit ampacity
- A fused disconnect cannot be used where the nameplate calls for an HACR breaker
Show the answer and the code reference
The answer
Nothing is wrong: 12 AWG conductors on 30 A fuses are correct for this condenser because its nameplate lists a 17.6 A minimum circuit ampacity and a 30 A maximum fuse.
Correct choice: 1. Nothing. This installation is compliant
Air-conditioning circuits are an exception to the small-conductor rule: 240.4(G) points to Article 440. There, conductors only have to meet the nameplate minimum circuit ampacity (440.35, marked per 440.4(B); here 125% of the 13.4 A RLA plus the 0.8 A fan, as in 440.33), and the overcurrent device may go up to the nameplate maximum so the compressor can start (440.22). 12 AWG copper (25 A at 75 C) exceeds the 17.6 A MCA, and the 30 A fuses do not exceed the 30 A maximum fuse on the nameplate. The disconnect is within sight, readily accessible with clear working space in front, Type 3R, not mounted on a service panel of the unit (440.14), and rated above the load (440.12). This is not a dwelling, so the 210.8(F) outdoor-outlet GFCI rule does not apply, and 210.8(B) covers only receptacles.
How to fix it
No correction needed. Confirm the fuses are a type the nameplate allows, and that the 210.63(A) service receptacle is within 25 ft on the same level.
Code references
NEC 2023 240.4(G) — Overcurrent Protection for Specific Conductor Applications
Conductors for specific applications listed in Table 240.4(G), including air-conditioning and refrigeration equipment circuit conductors, are protected per the referenced articles (Article 440, Parts III and VI) instead of the small-conductor limits of 240.4(D).
Drills citing 240.4(G)NEC 2023 440.22(C) — Protective Device Rating Not to Exceed the Manufacturer's Values
Where the maximum protective device rating marked by the manufacturer is less than the value calculated under 440.22(A) or (B), the protective device must not exceed the manufacturer's marked value.
Drills citing 440.22(C)NEC 2023 440.35 — Multimotor and Combination-Load Equipment
The ampacity of the conductors supplying multimotor and combination-load equipment must not be less than the minimum circuit ampacity marked on the equipment in accordance with 440.4(B).
Drills citing 440.35NEC 2023 440.14 — Location
The disconnecting means must be within sight from and readily accessible from the air-conditioning or refrigerating equipment, must meet the working space requirements of 110.26(A), and must not be on panels designed to allow access to the equipment.
Drills citing 440.14
2026 NEC:same rule and number. No 2026 change to 240.4(G) or Table 240.4(G), or to the Article 440 MCA/maximum-overcurrent rules (440.22, 440.35), was found; the 2026 conductor changes seen (16 AWG added in 310) do not touch this rule. Search snippets only. Confidence: low
Minnesota
Minnesota adopts the NEC without section amendments. The 2023 NEC applies to permits filed July 1, 2023 through Aug. 16, 2026, and the 2026 NEC to permits filed on or after Aug. 17, 2026 (Minn. Stat. 326B.35; Minn. Rules 1315.0200; DLI electrical codes and standards page). No Minnesota change to 240.4(G) or Article 440 is known.
How Minnesota adopts the NECWhy the other choices are wrong
- 12 AWG copper conductors may not be protected by 30 A fuses. 240.4(D) does not govern here: 240.4(G) sends air-conditioning circuits to Article 440. 12 AWG exceeds the 17.6 A MCA, and 30 A matches the nameplate maximum fuse.
- The fuses must not exceed the 17.6 A minimum circuit ampacity. MCA sizes the conductors; the nameplate maximum fuse or HACR breaker (here 30 A) sets the overcurrent limit (440.22(C)). Undersized fuses just blow on compressor start.
- A fused disconnect cannot be used where the nameplate calls for an HACR breaker. The nameplate says 'max fuse or HACR breaker'; either a fuse or an HACR-rated breaker is acceptable up to 30 A.