Garage subpanel with SER feeder
What's wrong here?
- Nothing. This installation is compliant
- The aluminum conductors must get antioxidant compound before landing in the lugs
- The neutral and equipment grounding conductors must be landed on the same bar
- 4 AWG aluminum is too small for a 50 A feeder
Show the answer and the code reference
The answer
Nothing is wrong: the 4 AWG aluminum SER feeder is adequately sized for its 50 A breaker and lands on lugs identified for aluminum, with the neutral isolated from the separate ground bar.
Correct choice: 1. Nothing. This installation is compliant
Aluminum feeders are permitted, and 110.14 requires only that each terminal be identified for the conductor material; every aluminum termination here (main lugs, neutral lug, ground-bar lug) is stamped AL9CU, meaning it is identified for aluminum or copper. Table 310.16 gives 4 AWG aluminum 55 A even in the 60°C column, so a 50 A feeder works where the cable or terminals are held to 60°C (338.10(B)(4)(a) for SE cable in thermal insulation, 110.14(C)(1)(a) for terminations of circuits rated 100 A or less), and the 6 AWG aluminum ground beats the 8 AWG aluminum minimum in Table 250.122 for a 60 A device. Because this is a feeder panel, not the service, the neutral bar is isolated on standoffs and the grounds land on a separate bar bonded to the can, as 250.142(B) and 250.24(A)(5) require. The branch circuits match too (12 AWG on 20 A, 14 AWG on 15 A); GFCI protection for the garage receptacles (210.8(A)(2)) is not visible here and is assumed to be at the receptacles.
How to fix it
No correction needed. Confirm the lug and breaker terminals were tightened to the manufacturer's marked torque with a calibrated torque tool (110.14(D)) and keep the panel label and circuit directory complete.
Code references
NEC 2023 110.14 — Electrical Connections
Pressure terminals and pressure splicing connectors must be identified for the material of the conductor (copper, aluminum, or copper-clad aluminum) and properly installed and used; dissimilar metals may not be mixed in one terminal unless it is identified for that.
Drills citing 110.14NEC 2023 Table 310.16 — Ampacities of Insulated Conductors in Raceway, Cable, or Earth
For aluminum or copper-clad aluminum, 4 AWG is listed at 55 A (60°C), 65 A (75°C), and 75 A (90°C).
Drills citing Table 310.16NEC 2023 110.14(C)(1)(a) — Temperature Limitations — Equipment Provisions
Termination provisions of equipment for circuits rated 100 A or less, or marked for 14 AWG through 1 AWG conductors, are used with 60°C conductors, or with higher-rated conductors whose ampacity is based on the 60°C column, unless the equipment is listed and identified for higher-temperature conductors.
Drills citing 110.14(C)(1)(a)NEC 2023 250.142(B) — Load-Side Equipment
Except as specifically permitted, the grounded (neutral) conductor may not be used to ground non-current-carrying metal parts of equipment on the load side of the service disconnecting means.
Drills citing 250.142(B)
2026 NEC:not yet checked Confidence: low
Minnesota
Minnesota adopted the 2023 NEC without amendment as the Minnesota Electrical Code (Minn. Rules 1315.0200; Minn. Stat. 326B.35), effective July 1, 2023, so 110.14, Table 310.16, and 250.142 apply as published. That edition governs permits filed through Aug. 16, 2026; permits filed on or after Aug. 17, 2026 fall under the 2026 NEC; see the 2026 NEC note on this drill for how the cited section fares there.
How Minnesota adopts the NECWhy the other choices are wrong
- The aluminum conductors must get antioxidant compound before landing in the lugs. The NEC does not require antioxidant compound. It is needed only where the terminal or conductor manufacturer's instructions call for it (110.3(B)), and AL9CU lugs are identified for aluminum as installed.
- The neutral and equipment grounding conductors must be landed on the same bar. Neutrals and grounds share a bar only where the main bonding jumper is, at the service disconnect. Downstream of the service, the grounded conductor may not be connected to equipment grounding conductors or the enclosure (250.24(A)(5), 250.142(B)), so separate, isolated bars are correct here.
- 4 AWG aluminum is too small for a 50 A feeder. Table 310.16 gives 4 AWG aluminum 55 A at 60°C and 65 A at 75°C, so it is adequate for a 50 A feeder even under the 60°C column.