Basement laundry tub
What's wrong here?
- The hose-thread spout on the tub faucet has no vacuum breaker, and the hose end sits under the water in the tub
- The washer box valves need hose-connection vacuum breakers
- A laundry tub may not drain through a P-trap; it must spill into the floor drain
- Nothing. This installation is compliant
Show the answer and the code reference
The answer
The utility faucet has a hose-thread spout with no vacuum breaker, and the hose connected to it lies below the water in the tub, creating a submerged inlet.
Correct choice: 1. The hose-thread spout on the tub faucet has no vacuum breaker, and the hose end sits under the water in the tub
UPC 603.5.7 requires every potable water outlet with a hose attachment, other than water heater drains, boiler drains and clothes washer connections, to be protected by a nonremovable hose bibb-type vacuum breaker or backflow preventer, or by an atmospheric vacuum breaker at least 6 in. above the highest point of use. This faucet has plain hose threads and no device. With the hose end lying in a tub of wash water, any drop in supply pressure (a main break, a hydrant flush, someone opening a big valve upstairs) can siphon that water back into the cold and hot lines. UPC 603.1 requires cross-connection control for exactly this situation.
How to fix it
Install a nonremovable hose-connection vacuum breaker on the spout threads (the type with a breakaway set screw), or replace the faucet with a utility faucet that has an integral vacuum breaker. Pull the hose out of the water; it should hang above the tub's flood rim.
Code references
UPC 2018 603.5.7 — Outlets with Hose Attachments
Potable water outlets with hose attachments, other than water heater drains, boiler drains and clothes washer connections, must be protected by a nonremovable hose bibb-type backflow preventer, a nonremovable hose bibb-type vacuum breaker, or an atmospheric vacuum breaker installed at least 6 in. above the highest point of usage on the discharge side of the last valve.
Drills citing 603.5.7UPC 2018 603.1 — General
Cross-connection control must be provided in accordance with Chapter 6. Equipment, mechanisms or substances that could pollute or contaminate the potable water supply are permitted only where the supply is protected by an approved backflow prevention device or assembly.
Drills citing 603.1
Minnesota
Minnesota adopts the 2018 Uniform Plumbing Code with Minnesota amendments as the Minnesota Plumbing Code (Minn. Rules ch. 4714, effective Dec. 17, 2021). Minnesota amends parts of UPC section 603 (reportedly in Minn. Rules 4714.0603), but no Minnesota amendment to 603.5.7 is known; check ch. 4714 before relying on it.
About the Minnesota Plumbing CodeWhy the other choices are wrong
- The washer box valves need hose-connection vacuum breakers. UPC 603.5.7 specifically exempts clothes washer connections from the hose-outlet vacuum breaker rule; the washer's own fill valve and air gap protect that connection.
- A laundry tub may not drain through a P-trap; it must spill into the floor drain. A laundry tub is a fixture and is trapped and vented like any other. Indirect waste to a floor drain is for things like water softener and condensate discharge, not a laundry tub.
- Nothing. This installation is compliant. Any potable outlet with hose threads (other than washer, water heater and boiler drain connections) needs a nonremovable hose-type vacuum breaker or backflow preventer, and here the hose is a submerged inlet sitting in dirty water.