Living room receptacle at trim-out
What's wrong here?
- The box is too small for the cables and device it holds
- No more than two cables may enter a single-gang box
- A 15 A duplex receptacle may not be connected to 12 AWG conductors
- Nothing. This installation is compliant
Show the answer and the code reference
The answer
The box is overfilled: its contents require 20.25 cubic inches, but the box is marked 18.0 cubic inches.
Correct choice: 1. The box is too small for the cables and device it holds
Count it per 314.16(B) using Table 314.16(B) (12 AWG = 2.25 cu in): six insulated conductors from three 12/2 cables count 6; all the equipment grounding conductors together count 1; the receptacle yoke counts 2, based on the 12 AWG conductors connected to it. That is 9 x 2.25 = 20.25 cu in. Pigtails that start and end inside the box and the wire connectors do not count, and this nonmetallic box has no internal clamps. A box stuffed past its rating nicks insulation, strains splices, and traps heat when the device is pushed back in.
How to fix it
Replace the box with one marked at least 20.25 cu in (a 20.3 cu in or larger single-gang old-work box, or a two-gang box), or move one cable's splice to a separate accessible box.
Code references
NEC 2023 314.16 — Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies
Boxes shall be large enough to provide free space for all enclosed conductors, and the box volume per 314.16(A) shall not be less than the fill calculated per 314.16(B).
Drills citing 314.16NEC 2023 314.16(B) — Box Fill Calculations
Each conductor that originates outside the box and terminates or is spliced inside counts once; conductors that do not leave the box are not counted; each device yoke counts twice based on the largest conductor connected to it; all equipment grounding conductors together count once based on the largest.
Drills citing 314.16(B)NEC 2023 Table 314.16(B) — Volume Allowance Required per Conductor
Gives the volume allowance per conductor: 2.00 cu in for 14 AWG and 2.25 cu in for 12 AWG.
Drills citing Table 314.16(B)NEC 2023 314.16(A)(2) — Other Boxes
Boxes of 100 cu in or less not described in Table 314.16(A), and nonmetallic boxes, shall be durably and legibly marked by the manufacturer with their volume.
Drills citing 314.16(A)(2)
2026 NEC:same rule and number. Rule and number kept. 2026 adds "splicing connectors" to the small fittings in 314.16(B) that need no box-fill allowance, which only confirms this drill's statement that wire connectors are not counted. Confidence: medium
Minnesota
Minnesota adopts the NEC by reference without amendment (Minn. Rules 1315.0200; Minn. Stat. 326B.35), so 314.16 applies as published. The 2023 NEC governs permits filed July 1, 2023 through Aug. 16, 2026; the 2026 NEC governs permits filed on or after Aug. 17, 2026 (exams moved to the 2026 NEC on Sept. 8, 2026). See the 2026 NEC note on this drill.
How Minnesota adopts the NECWhy the other choices are wrong
- No more than two cables may enter a single-gang box. The Code has no cable-count limit for a box; box fill volume under 314.16 is what governs.
- A 15 A duplex receptacle may not be connected to 12 AWG conductors. 12 AWG is fine on a 15 A device, and Table 210.21(B)(3) allows 15 A receptacles on a 20 A circuit with more than one receptacle.
- Nothing. This installation is compliant. Counted per 314.16(B), the contents need 9 x 2.25 = 20.25 cu in, more than the 18.0 cu in marked on the box.