Receptacle in a knotty pine wall
What's wrong here?
- The box is recessed behind the face of the wood paneling
- The gap around the box is over 1/8 in. and must be patched
- Only metal boxes are permitted in wood-paneled walls
- Nothing. This installation is compliant
Show the answer and the code reference
The answer
The box is recessed behind the face of the wood paneling; in a combustible surface the box, ring, or extender must be flush with the surface or project from it.
Correct choice: 1. The box is recessed behind the face of the wood paneling
314.20 lets a box sit back up to 1/4 in. in noncombustible finishes such as drywall, plaster, or tile. In walls of wood or other combustible material, the box front edge, plaster ring, extension ring, or listed extender must be flush with the finished surface or project from it. Here the paneling went up over boxes set for the original wall, so the box edge is set back by the thickness of the boards, leaving the raw wood of the cutout exposed to any heat or arcing at the device terminals. The receptacle ears resting on the pine do not cure it: 406.5(A) covers holding the yoke at the surface only for boxes set back as 314.20 permits, and in a combustible surface that setback is zero. This is common in Minnesota cabins and basements where tongue-and-groove pine went up over existing wiring.
How to fix it
Install a listed box extender or extension ring brought flush with the face of the paneling, then remount the receptacle to it and reinstall the faceplate.
Code references
NEC 2023 314.20 — Flush-Mounted Installations
In noncombustible surfaces such as concrete, tile, gypsum, or plaster, the front edge of the box, plaster ring, extension ring, or listed extender shall not be set back more than 1/4 in. from the finished surface. In walls or ceilings of wood or other combustible surface material, the box, ring, or listed extender shall be flush with the finished surface or project from it.
Drills citing 314.20NEC 2023 406.5(A) — Boxes That Are Set Back
Receptacles mounted in boxes set back of the finished surface as permitted by 314.20 shall be installed so the mounting yoke or strap is held rigidly at the finished surface.
Drills citing 406.5(A)
2026 NEC:same rule and number. No 2026 change to 314.20 turned up in Article 314 change summaries; the 1/4-in. setback for noncombustible surfaces and flush-or-project rule for combustible surfaces appear unchanged. Not confirmed against the 2026 text. Confidence: low
Minnesota
Minnesota adopts the NEC by reference without amendment (Minn. Rules 1315.0200; Minn. Stat. 326B.35), so 314.20 applies as published. The 2023 NEC governs permits filed July 1, 2023 through Aug. 16, 2026; the 2026 NEC governs permits filed on or after Aug. 17, 2026 (exams moved to the 2026 NEC on Sept. 8, 2026). See the 2026 NEC note on this drill.
How Minnesota adopts the NECWhy the other choices are wrong
- The gap around the box is over 1/8 in. and must be patched. The 1/8-in. gap repair rule in 314.21 is written for noncombustible surfaces such as drywall and plaster; the problem in wood is where the box edge sits.
- Only metal boxes are permitted in wood-paneled walls. Nonmetallic boxes are fine in combustible walls; what matters is that the box front edge, ring, or extender is flush with or projects from the wood.
- Nothing. This installation is compliant. The 1/4-in. setback allowance in 314.20 applies only to noncombustible surfaces. In wood or other combustible finishes the box must be flush or project.