New-house panel schedule
What's wrong here?
- The Bedroom 2 circuit has no AFCI protection
- The 30 A dryer circuit also needs AFCI protection
- The bath circuit needs a dual-function AFCI/GFCI breaker
- Nothing. This installation is compliant
Show the answer and the code reference
The answer
The 120 V, 15 A branch circuit serving Bedroom 2 is on a plain thermal-magnetic breaker with no AFCI protection.
Correct choice: 1. The Bedroom 2 circuit has no AFCI protection
210.12(B) requires AFCI protection for every 120-volt, 15- and 20-amp dwelling branch circuit feeding outlets in bedrooms, along with kitchens, living and family rooms, hallways, closets, laundry areas and similar rooms. Every other listed-area circuit in this panel is on a breaker with a TEST button, but Bedroom 2 is on a standard breaker, and the caption rules out AFCI receptacles downstream. Bedrooms are where cords get pinched under beds and space heaters run overnight, which is exactly the arcing fault an AFCI is built to catch. The furnace, garage and bath circuits are not in listed areas, and the 240 V range and dryer circuits are outside 210.12; those two carry GFCI because 210.8(D) requires it.
How to fix it
Replace the Bedroom 2 breaker with a listed combination-type AFCI (or dual-function) breaker that is listed for the panel, land the circuit neutral as the breaker instructions require, and test it.
Code references
NEC 2023 210.12(B) — Arc-Fault Circuit-Interrupter Protection: Dwelling Units
All 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling unit kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, or similar rooms or areas shall be protected by any of the means described in 210.12(A)(1) through (A)(6).
Drills citing 210.12(B)NEC 2023 210.12(A) — Arc-Fault Circuit-Interrupter Protection: Means of Protection
Lists the six permitted methods of providing AFCI protection, the first being a listed combination-type AFCI installed to protect the entire branch circuit; the others rely on an outlet branch-circuit AFCI at the first outlet, with conditions on the upstream device or the home-run wiring.
Drills citing 210.12(A)NEC 2023 210.8(D) — GFCI Protection: Specific Appliances
GFCI protection shall be provided for the branch circuit or outlet supplying listed appliances rated 150 volts or less to ground and 60 amperes or less, single- or 3-phase, including sump pumps, dishwashers, electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers and microwave ovens.
Drills citing 210.8(D)
2026 NEC:same rule and number. The dwelling AFCI rule and its list of rooms, bedrooms included, carry into the 2026 NEC. The notable 2026 edit is to Exception No. 2: the Jan. 1, 2025 sunset was removed, and it now also covers arc-welder outlets in garages and accessory buildings. That does not affect a bedroom circuit. Confidence: medium
Minnesota
Minnesota adopted the 2023 NEC without amendment (Minn. Stat. 326B.35; Minn. Rules 1315.0200), so 210.12(B) applies as published to permits filed July 1, 2023 through Aug. 16, 2026. Permits filed on or after Aug. 17, 2026 fall under the 2026 NEC; see the 2026 NEC note on this drill.
How Minnesota adopts the NECWhy the other choices are wrong
- The 30 A dryer circuit also needs AFCI protection. 210.12 covers only 120-volt, single-phase, 15- and 20-ampere branch circuits, so a 240 V, 30 A dryer circuit is outside it. The dryer does need GFCI protection under 210.8(D), which its two-pole breaker with a TEST button provides.
- The bath circuit needs a dual-function AFCI/GFCI breaker. Bathrooms are not among the dwelling areas listed in 210.12(B). They need GFCI protection under 210.8(A)(1), which the bath breaker provides.
- Nothing. This installation is compliant. Bedrooms are a listed AFCI area in 210.12(B), and the Bedroom 2 circuit has no AFCI device at the panel or, per the caption, at the outlets.