ElectricalGFCI, AFCI & receptacle devicesLevel 22023 NEC

Sump pump in an unfinished basement

Unfinished basement with a poured concrete foundation wall and floor. A sump basin with a black lid sits in the floor; a white PVC discharge pipe with a check valve rises from it to the rim joist. The pump cord runs up the wall to a GFCI receptacle in a surface-mounted steel 4-inch square box with a raised industrial cover, fed by EMT from the joists above, about 3 ft off the floor. A water heater stands at the right edge. TEST RESET
Unfinished basement, new house. The pump is the only load on this 20 A circuit.

What's wrong here?

  1. Nothing. This installation is compliant
  2. A sump pump must not be plugged into a GFCI receptacle
  3. The receptacle must be installed with the grounding hole up
  4. The sump pump needs its own disconnect switch within sight
Start this drill
Show the answer and the code reference

The answer

Nothing is wrong. The basement receptacle serving the sump pump is GFCI protected, readily accessible, and installed in a proper surface box and cover.

Correct choice: 1. Nothing. This installation is compliant

210.8(A)(5) requires GFCI protection for all 125-volt through 250-volt receptacles in dwelling basements, finished or not, and 210.8(D) separately requires it for the outlet supplying a sump pump. That is what is installed here: a GFCI receptacle a few feet up the wall, readily accessible for testing and resetting as 210.8 requires. EMT to a 4-inch square steel box with a raised device cover is a proper surface method on a concrete wall, and the plug and receptacle serve as the pump's disconnect per 422.33(A). Plenty of electricians still believe a sump pump must stay off GFCI, but the dedicated-appliance exceptions were dropped years ago.

How to fix it

No correction needed. Good practice is to add a battery-powered high-water alarm so a tripped GFCI or failed pump gets noticed.

Code references

  • NEC 2023 210.8(A)(5) — GFCI Protection, Dwelling Units: Basements

    In dwelling units, all 125-volt through 250-volt receptacles installed in basements, supplied by single-phase branch circuits rated 150 volts or less to ground, shall have GFCI protection. A receptacle supplying only a permanently installed fire alarm or burglar alarm system is excepted.

    Drills citing 210.8(A)(5)
  • NEC 2023 210.8(D) — GFCI Protection: Specific Appliances

    GFCI protection shall be provided for the branch circuit or outlet supplying listed appliances rated 150 volts or less to ground and 60 amperes or less, single- or 3-phase; sump pumps are on the list, along with dishwashers, ranges, clothes dryers and others.

    Drills citing 210.8(D)
  • NEC 2023 210.8 — Ground-Fault Circuit-Interrupter Protection for Personnel

    The ground-fault circuit interrupter shall be installed in a readily accessible location.

    Drills citing 210.8
  • NEC 2023 422.33(A) — Disconnection of Cord-and-Plug-Connected or Attachment Fitting-Connected Appliances: Separable Connector or Attachment Plug and Receptacle

    For cord-and-plug-connected appliances, an accessible separable connector or an accessible plug and receptacle shall be permitted to serve as the disconnecting means.

    Drills citing 422.33(A)

2026 NEC:not yet checked Confidence: low

Minnesota

MN adopts the NEC rule as writtenConfidence: medium

Minnesota adopted the 2023 NEC without amendment (Minn. Stat. 326B.35; Minn. Rules 1315.0200), so 210.8(A)(5) applies as published to permits filed July 1, 2023 through Aug. 16, 2026. Permits filed on or after Aug. 17, 2026 fall under the 2026 NEC; see the 2026 NEC note on this drill.

How Minnesota adopts the NEC

Why the other choices are wrong

  • A sump pump must not be plugged into a GFCI receptacle. That is an old myth: 210.8(A)(5) requires GFCI for basement receptacles with no sump pump exception, and 210.8(D) names sump pumps outright. A high-water alarm handles the nuisance-trip worry.
  • The receptacle must be installed with the grounding hole up. The NEC has no general rule on grounding-hole orientation for this receptacle. Ground-up is a preference or a local spec, not a Code requirement.
  • The sump pump needs its own disconnect switch within sight. For a cord-and-plug-connected appliance, the attachment plug and receptacle can serve as the disconnecting means under 422.33(A).
Code complianceLevel 2 · Journeyman#gfci#basement#sump-pump#receptacle#calibration

More in GFCI, AFCI & receptacle devices